Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2021, 09:35 AM
  • 2_1_2_11012021_014045.mp4

Date
01/11/2021
W/O
0870314
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00594
PipeID
P12632
Time
1:35 AM
Certificate
U-10114-0602254
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0369
Sewer Name
ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20210110MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Upstream MH
15 0854
Downstream MH
15 0853
Dir. of Survey
Downstream
Length Surveyed
287.6 ft.
Total Length
287.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3312
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0854 to 15 0853
MH: 15 0854MH: 15 0853downstream0 ft. MGO - General Observation - MH CONN 9:00 STUB0 ft. MGO - General Observation - MH CONN 3:00 OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 1:35AM5.3 ft. RFC - Roots Fine Connection, from 11 to 12 o'clock - 1%5.3 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6", 6" - OPEN-10% ROOTS96.2 ft. RFC - Roots Fine Connection, from 12 to 06 o'clock - 3%96.2 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE185.7 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 5 %, within 8 inches of joint: NO185.7 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6", 6" - ACTIVE- 25% ROOTS287.2 ft. MGO - General Observation - MH CONN 9:00 STUB287.6 ft. AMH - Downstream Manhole, Survey Ends - 2:00AM

Observations (11)

DistanceCodeObservation
96.2RFC3%
185.7RMC
5.3RFC1%
0MGOMH CONN 9:00 STUB
96.2TBAACTIVE
0MGOMH CONN 3:00 OPEN
0AMH1:35AM
5.3TBDOPEN-10% ROOTS
287.2MGOMH CONN 9:00 STUB
185.7TBDACTIVE- 25% ROOTS
287.6AMH2:00AM

Properties (6)

additional_info
POST CLEANING EVALUATION ONLY
customer
1
datetime
2021-01-11T01:35:51-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false
lining
PVCP