Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 15, 2021, 10:15 AM
  • 15 0778_15 0777_1152021_021800.mp4

Date
01/15/2021
W/O
0870364
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12979
Time
2:15 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1678R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20210115MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0778
Downstream MH
15 0777
Dir. of Survey
Downstream
Length Surveyed
386.1 ft.
Total Length
386.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0778 to 15 0777
MH: 15 0778MH: 15 0777downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active99.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-99% ROOTS101 ft. RMJ - Roots Medium Joint, from 12 to 01 o'clock, 10 %, within 8 inches of joint: YESR124.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-80% ROOTS386.1 ft. AMH - Downstream Manhole, Survey Ends - 2:45AM

Observation photos (1)

  • Roots Medium Joint, from 12 to 01 o'clock, 10 %, within 8 inches of joint: YESR

    101 ft. - Roots Medium Joint, from 12 to 01 o'clock, 10 %, within 8 inches of joint: YESR

Observations (8)

DistanceCodeObservation
99.8TFDOpen-99% ROOTS
386.1AMH2:45AM
124.4TFDOpen-80% ROOTS
0AMH2:25AM
101RMJ
0MWM
0MWL
0MGOConn. @ Mh, 3 O' Clock. Active

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2021-01-15T02:15:20-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false