Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2021, 08:30 AM
  • D 0099_D 0236_01072021_003946.mp4

Date
01/07/2021
W/O
864852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P26324
Time
12:30 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8350
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_864852_TV05171_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
D 0099
Downstream MH
D 0236
Dir. of Survey
Downstream
Length Surveyed
207.9 ft.
Total Length
207.9 ft.
Structural Index
3
Structural Quick
5G3G
Structural Rating
410
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
410
Pipe schematic from manhole D 0099 to D 0236
MH: D 0099MH: D 0236downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTING0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - D 00990 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. MGO - General Observation - 65% MAG COAT2.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start207.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish207.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish207.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/DEFECTIVE 45% GREASE-LATERAL/OPEN207.9 ft. AMH - Downstream Manhole, Survey Ends - D 0236207.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    3.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

Observations (14)

DistanceCodeObservation
3.4SRV
0MWL
2.5SAP
0MGOCONN @ MH 3 O'CLOCK/ACTING
0MGOCONN @ MH 9 O'CLOCK/OPEN
207.9SAP
0AMHD 0099
207.9SRV
2MGO65% MAG COAT
207.9MGOCONN @ MH 9 O'CLOCK/DEFECTIVE 45% GREASE-LATERAL/OPEN
0MWM
207.9AMHD 0236
2.5SSS
207.9SSS

Properties (6)

additional_info
630075010621201
custom_field_two
2
customer
1
datetime
2021-01-07T00:30:03-08:00
documentation
PROPIPE
is_lateral_inspection
false