Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2021, 09:09 AM
  • D 0123_D 0122_01042021_015113.mp4

Date
01/04/2021
W/O
864852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10032
Time
1:09 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8343
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_864852_TV05171_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
27 in.
Upstream MH
D 0123
Downstream MH
D 0122
Dir. of Survey
Downstream
Length Surveyed
434.9 ft.
Total Length
434.9 ft.
Structural Index
3
Structural Quick
5P3P
Structural Rating
850
O&M Index
2
O&M Quick
2P00
O&M Rating
172
Overall Index
3
Overall Quick
Overall Rating
1022
Pipe schematic from manhole D 0123 to D 0122
MH: D 0123MH: D 0122downstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01230 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 70% MAG COAT20 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start432 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish434 ft. MGO - General Observation - ROACHES @ MH434.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish434.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish434.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE434.9 ft. AMH - Downstream Manhole, Survey Ends - D 0122434.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    20 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
2.1SAP
2.1SSS
2.1MGO70% MAG COAT
434.8SAP
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
434.9SSS
0MWM
434.9MGOCONN @ MH 3 O'CLOCK/ACTIVE
434.9AMHD 0122
0AMHD 0123
432DAGS
0MWL
2DAGS
434MGOROACHES @ MH
20SRV
434.9SRV

Properties (7)

additional_info
630138010421001
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/SPALLIN
custom_field_two
2
customer
1
datetime
2021-01-04T01:09:27-08:00
documentation
PROPIPE
is_lateral_inspection
false