Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2021, 05:42 AM
  • D 0105_D 0104_01062021_215811.mp4

Date
01/06/2021
W/O
864852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10011
Time
9:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8350
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_864852_TV05171_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
57 in.
Upstream MH
D 0105
Downstream MH
D 0104
Dir. of Survey
Downstream
Length Surveyed
375.9 ft.
Total Length
375.9 ft.
Structural Index
3
Structural Quick
5M3N
Structural Rating
720
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
720
Pipe schematic from manhole D 0105 to D 0104
MH: D 0105MH: D 0104downstream0 ft. AMH - Upstream Manhole, Survey Begins - D 01050 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 65% MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start375 ft. MGO - General Observation - ROACHES @ MH375.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE375.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.9 ft. AMH - Downstream Manhole, Survey Ends - D 0104375.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish375.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    30.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMHD 0105
2.1SSS
30.8SRV
0MWL
2.1MGO65% MAG COAT
375MGOROACHES @ MH
375.9MGOCONN @ MH 9 O'CLOCK/ACTIVE
375.9SAP
375.9AMHD 0104
375.9SRV
375.9SSS
2.1SAP
0MWM

Properties (7)

additional_info
630075010621201
custom_field_three
AGGREGATE PROJECTING/SPALLING/REINFORCEMENT VISIBL
custom_field_two
2
customer
1
datetime
2021-01-06T21:42:51-08:00
documentation
PROPIPE
is_lateral_inspection
false