Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2021, 08:10 AM
  • D 0101_D 0100_01072021_002130.mp4

Date
01/07/2021
W/O
864852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10007
Time
12:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8350
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_864852_TV05171_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
57 in.
Upstream MH
D 0101
Downstream MH
D 0100
Dir. of Survey
Downstream
Length Surveyed
254.2 ft.
Total Length
254.2 ft.
Structural Index
3
Structural Quick
5H3I
Structural Rating
480
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
480
Pipe schematic from manhole D 0101 to D 0100
MH: D 0101MH: D 0100downstream0 ft. AMH - Upstream Manhole, Survey Begins - D 01010 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN0 ft. MWM - Water Mark, 25 %of cross sectional area2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - 70% MAG COAT24.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start254.2 ft. AMH - Downstream Manhole, Survey Ends - D 0100254.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN254.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

    24.9 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO, Start

Observations (13)

DistanceCodeObservation
0AMHD 0101
254.2AMHD 0100
254.2SSS
254.2MGOCONN @ MH 9 O'CLOCK/OPEN
254.2SAP
2.6SSS
254.2SRV
0MWL
2.6SAP
2.6MGO70% MAG COAT
0MGOCONN @ MH 9 O'CLOCK/OPEN
24.9SRV
0MWM

Properties (7)

additional_info
630075010621201
custom_field_three
AGGREGATE PROJECTING/SPALLING/REINFORCEMENT VISIBL
custom_field_two
2
customer
1
datetime
2021-01-07T00:10:35-08:00
documentation
PROPIPE
is_lateral_inspection
false