Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 06:03 AM
  • 01 0659B_01 0659A_12292020_222725.mp4

Date
12/29/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01161
Time
10:03 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0659B
Downstream MH
01 0659A
Dir. of Survey
Downstream
Length Surveyed
245.1 ft.
Total Length
245.1 ft.
Structural Index
4
Structural Quick
4G37
Structural Rating
187
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
187
Pipe schematic from manhole 01 0659B to 01 0659A
MH: 01 0659BMH: 01 0659Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 0659B2.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish75.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"83.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"122.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES168 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"170.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"243.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish244.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 & 9 OC'LOCK245.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0659A

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    38.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    122.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
243.6FM
168TFC
245.1AMH01 0659A
0MWM
0MWL
75.7TFC
122.1SSS
170.8TFC
244.7MGOCONNECTION AT THE MH 3 & 9 OC'LOCK
2.4CM
83.6TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
38.4FM
38.4CM
0AMH01 0659B

Properties (6)

custom_field_three
MULTIPLE FRACTURES
custom_field_two
3
customer
1
datetime
2020-12-29T22:03:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false