Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 06:38 AM
  • 01 0659_01 0658_12292020_224320.mp4

Date
12/29/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01159
Time
10:38 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0659
Downstream MH
01 0658
Dir. of Survey
Downstream
Length Surveyed
44.9 ft.
Total Length
44.9 ft.
Structural Index
2
Structural Quick
3728
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
37
Pipe schematic from manhole 01 0659 to 01 0658
MH: 01 0659MH: 01 0658downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06590 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3& 9 OC'LOCK4.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish44.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK44.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0658

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
4.5SSS
44.7MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH01 0659
7.6CM
42.8SSS
0MWL
0MWM
44.9AMH01 0658
42.8CM
0MGOCONNECTION AT THE MH 3& 9 OC'LOCK

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-29T22:38:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false