Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 08:05 AM
  • 01 0658_01 0657_12302020_002709.mp4

Date
12/30/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01158
Time
12:05 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0658
Downstream MH
01 0657
Dir. of Survey
Downstream
Length Surveyed
334.8 ft.
Total Length
334.8 ft.
Structural Index
3
Structural Quick
3L2E
Structural Rating
248
O&M Index
3
O&M Quick
413B
O&M Rating
43
Overall Index
3
Overall Quick
Overall Rating
291
Pipe schematic from manhole 01 0658 to 01 0657
MH: 01 0658MH: 01 0657downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06580 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 20 %of cross sectional area8.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.6 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start73.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"86.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"120.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"120.4 ft. RMJ - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Finish127.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"146.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish163.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"178.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"201.5 ft. RMC - Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES202.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"202.3 ft. RBL - Roots Ball Lateral, from 12 to 12 o'clock, 75 %204.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"240.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"245.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"284.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"286.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"292.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"320.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"324.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"331.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish334.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0657

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    12.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start

    61.6 ft. - Roots Medium Joint, from 07 to 05 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES

    201.5 ft. - Roots Medium Connection, at 02 o'clock, 10 %, within 8 inches of joint: YES

  • Roots Ball Lateral, from 12 to 12 o'clock, 75 %

    202.3 ft. - Roots Ball Lateral, from 12 to 12 o'clock, 75 %

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    240.9 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    292.5 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

Observations (28)

DistanceCodeObservation
146.5SSS
245.6TF
120.4TF
331.4CM
86.8TF
202.3TF
127.6TF
324.9TF
284.5TF
0AMH01 0658
0MWL
12.8CM
204.8TF
286.5TF
202.3RBL
292.5TB
120.4RMJ
240.9TB
334.8AMH01 0657
73.8TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWM
178.9TFC
8.2SSS
163.7TF
61.6RMJ
320.4TFC
201.5RMC

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-30T00:05:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false