Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 09:34 AM
  • 01 0654_01 0653_12302020_015632.mp4

Date
12/30/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01154
Time
1:34 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0654
Downstream MH
01 0653
Dir. of Survey
Downstream
Length Surveyed
300.3 ft.
Total Length
300.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
3
Overall Quick
Overall Rating
279
Pipe schematic from manhole 01 0654 to 01 0653
MH: 01 0654MH: 01 0653downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06540 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"11.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"25 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start38.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"41.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"84.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"87 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"87.6 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"107.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"155.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"156.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"184.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"209.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"227.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"250.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"251.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"263.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"284 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"286.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"289.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"297.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish300.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0653

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    13.7 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    25 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    87.6 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    155.9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    251.2 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    263.2 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    289.6 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

Observations (27)

DistanceCodeObservation
7.8TF
0AMH01 0654
11.4CM
25DAGS
286.3TFC
209.7TF
156.2TF
0MWM
184.2TFC
38.5TFC
263.2TB
87TF
13.7TB
0MWL
297.5CM
300.3AMH01 0653
155.9TB
87.6TB
227.7TFC
84.8TFC
251.2TB
289.6TB
297.5DAGS
107.8TFA
41.2TF
250.5TF
284TFC

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-30T01:34:46-08:00
documentation
PRO PIPE
is_lateral_inspection
false