Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 09:57 AM
  • 01 0653_01 0652_12302020_022005.mp4

Date
12/30/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01153
Time
1:57 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0653
Downstream MH
01 0652
Dir. of Survey
Downstream
Length Surveyed
282.1 ft.
Total Length
282.1 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
2J11
O&M Rating
111
Overall Index
2
Overall Quick
Overall Rating
276
Pipe schematic from manhole 01 0653 to 01 0652
MH: 01 0653MH: 01 0652downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06532.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8 ft. CM - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES10.4 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start10.4 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES27.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"29.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"38.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"40.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"65.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"68.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"105.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"108.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"116.1 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"139.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"142.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"177.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"190.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"223.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"226.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"241.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"279.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish279.1 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish282.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK282.1 ft. AMH - Downstream Manhole, Survey Ends - 01 0652

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    8 ft. - Crack Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    10.4 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

    38.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    40.5 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    116.1 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

Observations (27)

DistanceCodeObservation
223.7TFC
29.4TF
282.1MGOCONNECTION AT THE MH 9 OC'LOCK
65.3TF
226.1TF
2.3DAGS
177.9TFC
10.4CM
0MWL
139.2TF
108.8TF
279.1DAGS
279.1CM
38.4TB
0MWM
0AMH01 0653
241.7TFC
68.1TFC
142.3TF
8CM
282.1AMH01 0652
105.8TF
190.5TFC
10.4RFJ
116.1TB
40.5TB
27.2TF

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-30T01:57:29-08:00
documentation
PRO PIPE
is_lateral_inspection
false