Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 10:21 AM
  • 01 0652_01 1225_12302020_022739.mp4

Date
12/30/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01152
Time
2:21 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
01 0652
Downstream MH
01 1225
Dir. of Survey
Downstream
Length Surveyed
16.4 ft.
Total Length
16.4 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
3
O&M Quick
4123
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 01 0652 to 01 1225
MH: 01 0652MH: 01 1225downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06520 ft. MWL - Water Level, 10 %of cross sectional area1.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.7 ft. CS - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES11.9 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES14.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish16.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 & 9 OC'LOCK16.4 ft. AMH - Downstream Manhole, Survey Ends - 01 1225

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    1.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    6.7 ft. - Crack Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    11.9 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
11.9CM
14.4DAGS
1.8CM
16.4MGOCONNECTION AT THE MH 3 & 9 OC'LOCK
6.7CS
0MGOCONNECTION AT THE MH 9 OC'LOCK
16.4AMH01 1225
0MWM
0AMH01 0652
1.8DAGS
0MWL

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-30T02:21:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false