Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2020, 11:16 AM
  • 01 0649_01 0648_12302020_033817.mp4

Date
12/30/2020
W/O
864828
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00212
PipeID
P01148
Time
3:16 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8360
Sewer Name
01 MOUNTAIN VIEW-BELLE VERNON TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_864828_TV01110_DEC2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0649
Downstream MH
01 0648
Dir. of Survey
Downstream
Length Surveyed
373.5 ft.
Total Length
373.5 ft.
Structural Index
3
Structural Quick
513N
Structural Rating
227
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
3
Overall Quick
Overall Rating
375
Pipe schematic from manhole 01 0649 to 01 0648
MH: 01 0649MH: 01 0648downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 06490 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area4.3 ft. FS - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES4.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.6 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"44.3 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"44.3 ft. HSV - Hole Soil Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - PIPE BROKEN, POSSIBLE REPAIR VISIBLE84.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"87.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"107.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"123.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"125.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"133.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"138.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"193.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"214 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"259.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"287.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"307.8 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"372.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish372.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish373.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0648

Observation photos (7)

  • Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    4.3 ft. - Fracture Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    12.6 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    44.3 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Hole Soil Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - PIPE BROKEN, POSSIBLE REPAIR VISIBLE

    44.3 ft. - Hole Soil Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - PIPE BROKEN, POSSIBLE REPAIR VISIBLE

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    123.4 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

Observations (25)

DistanceCodeObservation
373.5AMH01 0648
133.1TF
107.9TF
287.2TF
307.8TFA
44.3TB
0MGOCONNECTION AT THE MH 3 OC'LOCK
123.4TB
372.2CM
12.6TB
84.8TFC
0AMH01 0649
214TF
4.3FS
372.2DAGS
0MWM
259.7TF
4.3DAGS
44.3HSVPIPE BROKEN, POSSIBLE REPAIR VISIBLE
0MWL
87.6TFC
125.5TFC
193.9TF
7.6CM
138.2TF

Properties (6)

custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-30T03:16:09-08:00
documentation
PRO PIPE
is_lateral_inspection
false