Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2020, 08:32 AM
  • 2_1_3_10032020_032116.mp4

Date
03/10/2020
W/O
0818533
Weather
Heavy Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00208
PipeID
P00923
Time
1:32 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0323
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20200310MDM_HOLMES_WILLOWBROOK_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
01 0442
Downstream MH
01 0441
Dir. of Survey
Downstream
Length Surveyed
346.9 ft.
Total Length
346.9 ft.
Structural Index
3
Structural Quick
4N2M
Structural Rating
432
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
446
Pipe schematic from manhole 01 0442 to 01 0441
MH: 01 0442MH: 01 0441downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE4.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE24.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE29.7 ft. TFD - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-SEVERE CRACKS33.3 ft. MWM - Water Mark, 30 %of cross sectional area33.3 ft. MWL - Water Level, 10 %of cross sectional area55.9 ft. MWM - Water Mark, 20 %of cross sectional area55.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE55.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE55.9 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG55.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG55.9 ft. MWL - Water Level, 5 %of cross sectional area62.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG68.2 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - ACTIVE-1"INTRUDING78.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE81.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB94.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN116 ft. SSS - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - DEEP CORROSON127.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB128.3 ft. TBI - Tap Break-In Intruding, at 10 o'clock, -, -, within 8 inches of joint: YES, 6", 1" - OPEN-1" INTRUDING137.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN183.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB183.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN194.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN202.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN220 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN223.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE245.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN268.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB274.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN291.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN310.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE318.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE322.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN346.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE346.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN346.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG346.9 ft. AMH - Downstream Manhole, Survey Ends - 4:10AM

Observation photos (10)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-SEVERE CRACKS

    29.7 ft. - Tap Factory Made Defective, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE-SEVERE CRACKS

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

    55.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    55.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    62.9 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - DEEP CORROSON

    116 ft. - Surface Spalling, from 02 to 04 o'clock, within 8 inches of joint: YES - DEEP CORROSON

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE

    223.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE

    310.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - MODERATE

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE

    318.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES - SEVERE

Observations (42)

DistanceCodeObservation
4.5DSZSLUDGE
2.5SSSBLISTERING PEELING CONCRETE
183.8TFOPEN
127.2TFCSTUB
94.3TFOPEN
310.2FMMODERATE
194.1TFOPEN
318.5FMSEVERE
116SSSDEEP CORROSON
202.1TFOPEN
346.8SSSBLISTERING PEELING CONCRETE
137.2TFOPEN
55.9MWM
78.3TFAACTIVE
268.1TFCSTUB
81.3TFCSTUB
223.3FMMODERATE
346.8TFOPEN
29.7TFDACTIVE-SEVERE CRACKS
33.3MWM
55.9SSSBLISTERING PEELING CONCRETE
55.9SSSBLISTERING FLAKING CONCRETE
220TFOPEN
274.7TBOPEN
291.9TFOPEN
55.9SAMSEVERE AGG
128.3TBIOPEN-1" INTRUDING
0MWL
0MWM
245.4TFOPEN
55.9SAMSEVERE AGG
55.9MWL
183.1TFCSTUB
24.7DSZSLUDGE
33.3MWL
346.8SAMSEVERE AGG
62.9SAMSEVERE AGG
346.9AMH4:10AM
322.5TFOPEN
2SAMSEVERE AGG
68.2TBIACTIVE-1"INTRUDING
0AMH3:20AM

Properties (6)

custom_field_three
SEVERE AGG MISSING - DEEP CORROSON
custom_field_two
2
customer
LACSD
datetime
2020-03-10T01:32:18-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false