Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2020, 07:45 AM
  • 05 0637_05 0636_12102020_235532.mp4

Date
12/10/2020
W/O
859962
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00509
PipeID
P05862
Time
11:45 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8329
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
05
Purpose
Routine Assessment
Project
WO_859962_TV05095_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
10 in.
Upstream MH
05 0637
Downstream MH
05 0636
Dir. of Survey
Downstream
Length Surveyed
431.4 ft.
Total Length
431.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 0637 to 05 0636
MH: 05 0637MH: 05 0636downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 06370 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start431.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish431.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0636

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.1MGOMAG COAT
0AMH05 0637
0MGOCONNECTION AT MH 3 O'CLOCK
2.1SAV
431.4SAV
0MWM
431.4AMH05 0636
0MWL

Properties (7)

additional_info
630075121020201
custom_field_three
AGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2020-12-10T23:45:22-08:00
documentation
PROPIPE
is_lateral_inspection
false