Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2020, 07:36 AM
  • 05 2189_05 2188_12142020_234820.mp4

Date
12/14/2020
W/O
859962
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00509
PipeID
P07332
Time
11:36 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8331
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_859962_TV05095_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
05 2189
Downstream MH
05 2188
Dir. of Survey
Downstream
Length Surveyed
430.6 ft.
Total Length
430.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 2189 to 05 2188
MH: 05 2189MH: 05 2188downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 21890 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT430.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED430.6 ft. AMH - Downstream Manhole, Survey Ends - 05 2188430.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
0AMH05 2189
430.6MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MWL
430.6AMH05 2188
2.2SAV
2.2MGOMAG COAT
430.6SAV

Properties (8)

additional_info
630075121420201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2020-12-14T23:36:44-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26577