Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2020, 11:16 AM
  • 05 2203_05 2202A_12142020_032225.mp4

Date
12/14/2020
W/O
859962
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00509
PipeID
P07348
Time
3:16 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8330
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_859962_TV05095_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
10 in.
Upstream MH
05 2202A
Downstream MH
05 2203
Dir. of Survey
Upstream
Length Surveyed
209.3 ft.
Total Length
209.3 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
2
O&M Quick
2F00
O&M Rating
70
Overall Index
3
Overall Quick
Overall Rating
193
Pipe schematic from manhole 05 2202A to 05 2203
MH: 05 2202AMH: 05 2203upstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 05 22030 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish4.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish176.8 ft. DSGV - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start207.2 ft. MGO - General Observation - MAG COAT207.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start209.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK209.3 ft. MWM - Water Mark, 20 %of cross sectional area209.3 ft. MWL - Water Level, 10 %of cross sectional area209.3 ft. AMH - Downstream Manhole, Survey Begins - 05 2202A

Observation photos (1)

  • Deposits Settled Gravel,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    32.5 ft. - Deposits Settled Gravel, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2.1MGOMAG COAT
0MWM
205SAV
209.3MGOCONNECTION AT MH 3 O'CLOCK
0MWL
209.3AMH05 2203
0.1MGOCONNECTION AT MH 9 O'CLOCK
32.5DSGV
209.3DSGV
0AMH05 2202A
2SAV

Properties (8)

additional_info
63009812142001
custom_field_three
AGG
custom_field_two
3
customer
1
datetime
2020-12-14T03:16:13-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26577