Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2020, 08:29 AM
  • 32 1032_32 1031_12112020_004438.mp4

Date
12/11/2020
W/O
864845
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19480
Time
12:29 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8277
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_864845_TV32002_DEC2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1032
Downstream MH
32 1031
Dir. of Survey
Downstream
Length Surveyed
347.2 ft.
Total Length
347.2 ft.
Structural Index
4
Structural Quick
4L31
Structural Rating
267
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
405
Pipe schematic from manhole 32 1032 to 32 1031
MH: 32 1032MH: 32 1031downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10322 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES13.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start200.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"345.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish345.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish347.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1031

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    13.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWL
347.2AMH32 1031
2DAGS
345.7DAGS
9CM
0MWM
0AMH32 1032
13.5FM
200.1TB
345.7FM

Properties (7)

additional_info
630069121020203
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-12-11T00:29:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false