Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2017, 10:05 AM
  • 29 0321_29 0320 _26072017_030819.mp4

Date
07/26/2017
W/O
646910
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z01024
PipeID
P24338
Time
3:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4763
Sewer Name
29 PACIFIC COAST HIGHWAY TRUNK
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
WO_646910_TV29082_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0321
Downstream MH
29 0320
Dir. of Survey
Downstream
Length Surveyed
322.9 ft.
Total Length
322.9 ft.
Structural Index
3
Structural Quick
3N27
Structural Rating
239
O&M Index
4
O&M Quick
4A31
O&M Rating
51
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 29 0321 to 29 0320
MH: 29 0321MH: 29 0320downstream0 ft. MMC - Material Change, Concrete pipe (non-reinfored)0 ft. AMH - Upstream Manhole, Survey Begins - 29 03210 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start112.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"116.7 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES133.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES186.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES193.6 ft. TBI - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: YES, 6", 1"208.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"217.5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES220.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES228 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES235.8 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES240.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES243.3 ft. MCU - Camera Underwater, Start272.1 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES277.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES279.8 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start304.1 ft. MCU - Camera Underwater, Finish320.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish320.1 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish322.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK322.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0320

Observation photos (1)

  • Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

    193.6 ft. - Tap Break-In Intruding, at 03 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

Observations (26)

DistanceCodeObservation
320.1SAV
2.1SAV
322.9MGOCONNECTION AT MH 3 O'CLOCK
279.8CM
0MMC
235.8CL
277.1CL
220.3CL
193.6TBI
322.9AMH29 0320
304.1MCU
133.2FL
240.9CL
320.1CM
208.5TFC
243.3MCU
272.1CM
228CL
186.6CL
116.7CS
217.5CM
0AMH29 0321
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
112.7TF
0MWM

Properties (6)

additional_info
SC345523
custom_field_two
3
customer
LACSD
datetime
2017-07-26T03:05:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false