Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2017, 11:03 AM
  • 29 0319_29 0318 _26072017_040425.mp4

Date
07/26/2017
W/O
646910
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z01024
PipeID
P24336
Time
4:03 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4763
Sewer Name
29 PACIFIC COAST HIGHWAY TRUNK
City
SIGNAL HILL
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
WO_646910_TV29082_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0319
Downstream MH
29 0318
Dir. of Survey
Downstream
Length Surveyed
278.5 ft.
Total Length
278.6 ft.
Structural Index
3
Structural Quick
3J26
Structural Rating
183
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
183
Pipe schematic from manhole 29 0319 to 29 0318
MH: 29 0319MH: 29 0318downstream0 ft. MMC - Material Change, Concrete pipe (non-reinfored)0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 03190 ft. MWM - Water Mark, 10 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start32.6 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"34.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES62.7 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES65.4 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES96.5 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES100.3 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6"117.3 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES120 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES216.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 6"218.4 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES267.5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES277 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish278.6 ft. AMH - Downstream Manhole, Survey Ends - 29 0318

Observations (18)

DistanceCodeObservation
218.4FL
0MMC
278.6AMH29 0318
34.2CL
0MWL
277SAV
65.4CL
267.5CM
100.3TFA
120CL
117.3CL
62.7CL
96.5CL
0AMH29 0319
2.6SAV
32.6TFA
216.9TF
0MWM

Properties (6)

additional_info
SC345523
custom_field_two
3
customer
LACSD
datetime
2017-07-26T04:03:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false