Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2021, 11:13 AM
  • D 0211_D 0123_01042021_034804.mp4

Date
01/04/2021
W/O
865322
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10033
Time
3:13 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8344
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
REDONDO BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_865322_TV05172_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Square
Height
30 in.
Width
27 in.
Upstream MH
D 0211
Downstream MH
D 0123
Dir. of Survey
Downstream
Length Surveyed
311.1 ft.
Total Length
311.1 ft.
Structural Index
3
Structural Quick
5K3K
Structural Rating
620
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
620
Pipe schematic from manhole D 0211 to D 0123
MH: D 0211MH: D 0123downstream0 ft. MGO - General Observation - CONNECTION AT MH, 6 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 02112.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start311.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.1 ft. AMH - Downstream Manhole, Survey Ends - D 0123311.1 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK311.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2.1SSS
311.1SSS
311.1SAP
0MGOCONNECTION AT MH, 6 O'CLOCK
311.1AMHD 0123
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWL
2.1MGOMAG COAT
311.1MGOCONNECTION AT MH, 9 O'CLOCK
0MWM
2.1SRV
2.1SAP
0AMHD 0211
311.1SRV

Properties (7)

additional_info
630138010421002
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/SPALLIN
custom_field_two
2
customer
1
datetime
2021-01-04T03:13:52-08:00
documentation
PROPIPE
is_lateral_inspection
false