Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2021, 10:27 AM
  • D 0107_D 0106_01062021_024836.mp4

Date
01/06/2021
W/O
865322
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10013
Time
2:27 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8349
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_865322_TV05172_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
51 in.
Upstream MH
D 0107
Downstream MH
D 0106
Dir. of Survey
Downstream
Length Surveyed
557.1 ft.
Total Length
557.1 ft.
Structural Index
3
Structural Quick
523U
Structural Rating
565
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
565
Pipe schematic from manhole D 0107 to D 0106
MH: D 0107MH: D 0106downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 01072.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. MGO - General Observation - MAG COAT219.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES505.7 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO557.1 ft. AMH - Downstream Manhole, Survey Ends - D 0106557.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish557.1 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK557.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    219.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO

    505.7 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: NO

Observations (14)

DistanceCodeObservation
219.8SRV
0MGOCONNECTION AT MH, 9 O'CLOCK
505.7SRV
0MGOCONNECTION AT MH, 3 O'CLOCK
0MWL
557.1AMHD 0106
0MWM
557.1SAP
557.1MGOCONNECTION AT MH, 3 O'CLOCK
557.1SSS
2.3SAP
2.4SSS
0AMHD 0107
2.4MGOMAG COAT

Properties (7)

additional_info
630075010521202
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-01-06T02:27:36-08:00
documentation
PROPIPE
is_lateral_inspection
false