Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2021, 10:00 AM
  • D 0097_D 0096_01072021_021220.mp4

Date
01/07/2021
W/O
865322
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00156
PipeID
P10003
Time
2:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8451
Sewer Name
D JOINT OUTFALL D - UNIT 6
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_865322_TV05172_DEC2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
57 in.
Upstream MH
D 0097
Downstream MH
D 0096
Dir. of Survey
Downstream
Length Surveyed
310 ft.
Total Length
310 ft.
Structural Index
3
Structural Quick
5J3K
Structural Rating
570
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
570
Pipe schematic from manhole D 0097 to D 0096
MH: D 0097MH: D 0096downstream0 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - D 00972.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start302.2 ft. TS - Tap Saddle, at 03 o'clock, -, within 8 inches of joint: NO, 6"310 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish310 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK310 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish310 ft. AMH - Downstream Manhole, Survey Ends - D 0096

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    2.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

    44.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: NO, Start

  • Tap Saddle, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    302.2 ft. - Tap Saddle, at 03 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
0MGOCONNECTION AT MH, 3 O'CLOCK
310SAP
302.2TS
0MGOCONNECTION AT MH, 9 O'CLOCK
310SRV
0MWM
44.1SRV
0MWL
310MGOCONNECTION AT MH, 9 O'CLOCK
310SSS
310AMHD 0096
2.8SSS
2.8SAP
0AMHD 0097

Properties (7)

additional_info
630075010521202
custom_field_three
AGGREGATE PROJECTING/SPALLING/REINFORCEMENT VISIBL
custom_field_two
2
customer
1
datetime
2021-01-07T02:00:34-08:00
documentation
PROPIPE
is_lateral_inspection
false