Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2021, 08:27 AM
  • 05 2155_05 2304_152021_010808.mp4

Date
01/06/2021
W/O
0872718
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00479
PipeID
P07297
Time
12:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1687
Sewer Name
05 MADISON STREET TRUNK
City
PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
35
Purpose
Routine Assessment
Project
20210106MDM_MADISON_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
7.5 in.
Upstream MH
05 2155
Downstream MH
05 2304
Dir. of Survey
Downstream
Length Surveyed
353.3 ft.
Total Length
353.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 05 2155 to 05 2304
MH: 05 2155MH: 05 2304downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active8 ft. MGO - General Observation - 7.5" VCP-PVC102.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Open205.9 ft. MGO - General Observation - 7.5" VCP-PVC350 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - Active353.3 ft. AMH - Downstream Manhole, Survey Ends - 1:25AM

Observation photos (2)

  • General Observation - 7.5" VCP-PVC

    8 ft. - General Observation - 7.5" VCP-PVC

  • General Observation - 7.5" VCP-PVC

    205.9 ft. - General Observation - 7.5" VCP-PVC

Observations (9)

DistanceCodeObservation
0MWM
205.9MGO7.5" VCP-PVC
0AMH12:55AM
8MGO7.5" VCP-PVC
0MWL
353.3AMH1:25AM
102.7TBOpen
0MGOConn. @ Mh, 3 O' Clock. Active
350TBActive

Properties (7)

custom_field_three
LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2021-01-06T00:27:47-08:00
documentation
MARTIN,CASTILLO,RUVALCABA
is_lateral_inspection
false
lining
PVC