Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 22, 2020, 10:25 AM
  • 05 0818_05 0817_12222020_025014.mp4

Date
12/22/2020
W/O
860420
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00419
PipeID
P06048
Time
2:25 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8357
Sewer Name
05 ARLINGTON AVENUE EXTENSION TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_860420_TV05374_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
21 in.
Upstream MH
05 0818
Downstream MH
05 0817
Dir. of Survey
Downstream
Length Surveyed
244.6 ft.
Total Length
244.6 ft.
Structural Index
3
Structural Quick
5143
Structural Rating
56
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
56
Pipe schematic from manhole 05 0818 to 05 0817
MH: 05 0818MH: 05 0817downstream0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 08180 ft. MWM - Water Mark, 30 %of cross sectional area6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES13.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES23.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"25.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"70.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"73.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"124.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"126.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"168.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES173.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"175 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES175.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"189.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES193.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start218.2 ft. B - Broken, from 07 to 02 o'clock, within 8 inches of joint: NO - REPAIR VISIBLE219.6 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: NO222.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"225.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"241.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish244.6 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK244.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0817

Observation photos (8)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    13.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    168.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    175 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    189.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    193.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 07 to 02 o'clock, within 8 inches of joint: NO - REPAIR VISIBLE

    218.2 ft. - Broken, from 07 to 02 o'clock, within 8 inches of joint: NO - REPAIR VISIBLE

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: NO

    219.6 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: NO

Observations (25)

DistanceCodeObservation
175.9TF
0MGOCONNECTION AT MH, 9 O'CLOCK
13.8CM
23.2TFC
126.8TFC
173.3TFC
225.2TFC
219.6FM
222.6TFC
168.2CM
218.2BREPAIR VISIBLE
6FM
244.6MGOCONNECTION AT MH, 9 O'CLOCK
241.2CM
193.5CM
25.5TFC
244.6AMH05 0817
70.6TFC
124.1TFC
73.2TFC
175FM
0MWL
189.5CM
0AMH05 0818
0MWM

Properties (6)

custom_field_three
CRACKS, FRACTURES, BROKEN PIPE
custom_field_two
2
customer
1
datetime
2020-12-22T02:25:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false