Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2020, 05:36 AM
  • 02 1624_02 1623_12152020_214934.mp4

Date
12/15/2020
W/O
860128
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00235
PipeID
P04644
Time
9:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8284
Sewer Name
02 ATLANTIC AVENUE TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_860128_TV02356_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1624
Downstream MH
02 1623
Dir. of Survey
Downstream
Length Surveyed
318.2 ft.
Total Length
318.2 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
309
Pipe schematic from manhole 02 1624 to 02 1623
MH: 02 1624MH: 02 1623downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 16240 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6 ft. MGO - General Observation - ROUGH SURFACE / SPALLING(?) (VCP) -THROUGHOUT - 8 TO 4 O'CLOCK10.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start92.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish316.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE318.2 ft. AMH - Downstream Manhole, Survey Ends - 02 1623

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    318.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
291.7TFA
0AMH02 1624
0MGOCOCKROACHES IN MANHOLE
0MWM
318.2MGOCOCKROACHES IN MANHOLE
316.3DAGS
115.8TFA
2DAGS
6MGOROUGH SURFACE / SPALLING(?) (VCP) -THROUGHOUT - 8 TO 4 O'CLOCK
0MWL
92.1TFA
161.2TFA
318.2AMH02 1623
316.3CM
10.4CM
240.3TFA

Properties (7)

additional_info
630069121520201
custom_field_three
MULTIPLE CRACKS - ROUGH SURFACE
custom_field_two
2
customer
1
datetime
2020-12-15T21:36:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false