Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2020, 08:04 AM
  • 01 0001_G 0072_12232020_000815.mp4

Date
12/23/2020
W/O
860511
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00209
PipeID
P02145
Time
12:04 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8088
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
WO_860511_TV01050_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
33 in.
Width
18 in.
Upstream MH
01 0001
Downstream MH
G 0072
Dir. of Survey
Downstream
Length Surveyed
22.5 ft.
Total Length
22.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0001 to G 0072
MH: 01 0001MH: G 0072downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00010 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE4.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start18.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish22 ft. MGO - General Observation - ROACHES @ MH22.5 ft. AMH - Downstream Manhole, Survey Ends - G 0072

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    4.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
0AMH01 0001
22.5AMHG 0072
4.1DAGS
22MGOROACHES @ MH
0MWM
18.9DAGS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (8)

additional_info
630069122220101
custom_field_three
LIGHT GREASE/LINER WRINKLED
custom_field_two
3
customer
1
datetime
2020-12-23T00:04:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
CIPP