Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2020, 06:58 AM
  • 05 1149_05 1148_12152020_233506.mp4

Date
12/15/2020
W/O
859967
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00436
PipeID
P06388
Time
10:58 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8332
Sewer Name
05 EAST ROSECRANS AVENUE TRUNK, SECTION 1
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_859967_TV05270_NOV2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1148
Downstream MH
05 1149
Dir. of Survey
Upstream
Length Surveyed
305.1 ft.
Total Length
305.1 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
363
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
363
Pipe schematic from manhole 05 1148 to 05 1149
MH: 05 1148MH: 05 1149upstream0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 11490 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 12 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 1 OC'LOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish74.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start303.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start305.1 ft. MWM - Water Mark, 25 %of cross sectional area305.1 ft. AMH - Downstream Manhole, Survey Begins - 05 1148305.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK (NOTE: THIS CONNECTION IS NOT EVIDENT ON VIDEO).305.1 ft. MWL - Water Level, 20 %of cross sectional area305.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK (NOTE: THIS CONNECTION IS NOT EVIDENT ON VIDEO).

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    230.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
305.1SAP
305.1AMH05 1149
0MWM
0AMH05 1148
0MGOCONNECTION AT THE MH 3 OC'LOCK (NOTE: THIS CONNECTION IS NOT EVIDENT ON VIDEO).
305.1MGOACTIVE CONNECTION AT THE MH 12 OC'LOCK
305.1MGOCONNECTION AT THE MH 1 OC'LOCK
0MWL
305.1MGOACTIVE CONNECTION AT THE MH 9 OC'LOCK
230.9TFC
171.4TF
0MGOCONNECTION AT THE MH 9 OC'LOCK (NOTE: THIS CONNECTION IS NOT EVIDENT ON VIDEO).
2SAP
71.8TFC
2.7CM
98.9TF
305.1MGOCONNECTION AT THE MH 3 OC'LOCK
305.1CM

Properties (7)

additional_info
630098121520201
custom_field_three
AGGREGATE PROJECTING/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2020-12-15T22:58:56-08:00
documentation
PROPIPE
is_lateral_inspection
false