Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2020, 06:24 AM
  • 16 0186_16 0280_10202020_000427.mp4

Date
10/19/2020
W/O
849892
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00654
PipeID
P13329
Time
11:24 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8129
Sewer Name
CHAPEL AVENUE TRUNK, SECTION 3
City
SOUTH PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_849892_TV16019_SEP2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0186
Downstream MH
16 0280
Dir. of Survey
Downstream
Length Surveyed
59.3 ft.
Total Length
59.3 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
55
O&M Index
2
O&M Quick
412A
O&M Rating
26
Overall Index
2
Overall Quick
Overall Rating
81
Pipe schematic from manhole 16 0186 to 16 0280
MH: 16 0186MH: 16 0280downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 01860 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 40 %of cross sectional area2 ft. MGO - General Observation - 45% MAG COAT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish57 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish59.3 ft. AMH - Downstream Manhole, Survey Ends - 16 028059.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN59.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
2.1SAV
2MGO45% MAG COAT
57DAGS
0AMH16 0186
2DAGS
59.3AMH16 0280
0MWM
57SSS
2SSS
59.3MGOCONN @ MH 3 O'CLOCK/UNKNOWN
59.3SAV
0MWL

Properties (7)

additional_info
6301019200075P2
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2020-10-19T23:24:09-07:00
documentation
PROPIPE
is_lateral_inspection
false