Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 23, 2020, 11:19 AM
  • 05 0337_05 0453_12232020_034138.mp4

Date
12/23/2020
W/O
859976
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00499
PipeID
P05667
Time
3:19 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8359
Sewer Name
05 OAK STREET-CENTER AVENUE RELIEF TRUNK
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Routine Assessment
Project
WO_859976_TV05188_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
22 in.
Upstream MH
05 0453
Downstream MH
05 0337
Dir. of Survey
Upstream
Length Surveyed
98.5 ft.
Total Length
98.5 ft.
Structural Index
2
Structural Quick
2C00
Structural Rating
38
O&M Index
3
O&M Quick
3C00
O&M Rating
57
Overall Index
3
Overall Quick
Overall Rating
95
Pipe schematic from manhole 05 0453 to 05 0337
MH: 05 0453MH: 05 0337upstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 03370 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"96.5 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start96.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start98.5 ft. MWM - Water Mark, 35 %of cross sectional area98.5 ft. MWL - Water Level, 30 %of cross sectional area98.5 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK98.5 ft. AMH - Downstream Manhole, Survey Begins - 05 0453

Observation photos (3)

  • Deposits Settled Compacted,  15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Settled Compacted, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    96.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

Observations (10)

DistanceCodeObservation
2DSC
96.9TB
98.5SSS
98.5AMH05 0337
0MWM
98.5DSC
0MWL
0MGOCONNECTION AT MH, 3 O'CLOCK
2SSS
0AMH05 0453

Properties (6)

custom_field_three
SPALLING, DEBRIS
custom_field_two
2
customer
1
datetime
2020-12-23T03:19:31-08:00
documentation
PRO PIPE
is_lateral_inspection
false