Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 4, 2021, 07:27 AM
  • 18 0867_18 0866_132021_234817.mp4

Date
01/03/2021
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00709
PipeID
P14719
Time
11:27 PM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1684
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
NORWALK
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Maintenance Related
Project
20210103MDM_SO_WHITTIER_OUTFALL_RLF_TR_SECTS_1_2A_2B_2C_3
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
18 0867
Downstream MH
18 0866
Dir. of Survey
Downstream
Length Surveyed
15.2 ft.
Total Length
15.2 ft.
Structural Index
5
Structural Quick
5541
Structural Rating
29
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
34
Pipe schematic from manhole 18 0867 to 18 0866
MH: 18 0867MH: 18 0866downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 11:40AM0 ft. MWL - Water Level, 20 %of cross sectional area0.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REWBAR CORRODED & MISSING2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG10.8 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SOIL VISIBLE 2 VOIDS10.8 ft. MGP - General Photograph - SIDE SUPPORTS INSIDE VOID AT 12:0010.8 ft. MGP - General Photograph - LOOKING UP THROUGH VOID TO METAL PLATES10.8 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE SECOND VOID AT 12:0010.8 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE VOID TO SURFACE14.8 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SOIL VISIBLE 2 VOIDS14.8 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG14.8 ft. SMW - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - 2 VOIDS AT 12:0014.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR CORRODED & MISSING15.2 ft. MSA - Survey Abandoned - DOWNLEG UPSTREAM SIPHON(12:30AM}

Observation photos (6)

  • General Photograph - SIDE SUPPORTS INSIDE VOID AT 12:00

    10.8 ft. - General Photograph - SIDE SUPPORTS INSIDE VOID AT 12:00

  • General Photograph - LOOKING UP THROUGH VOID TO METAL PLATES

    10.8 ft. - General Photograph - LOOKING UP THROUGH VOID TO METAL PLATES

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE SECOND VOID AT 12:00

    10.8 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE SECOND VOID AT 12:00

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE VOID TO SURFACE

    10.8 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - SOIL VISIBLE VOID TO SURFACE

  • Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - 2 VOIDS AT 12:00

    14.8 ft. - Surface Missing Wall, from 10 to 02 o'clock, within 8 inches of joint: NO - 2 VOIDS AT 12:00

  • Survey Abandoned - DOWNLEG UPSTREAM SIPHON(12:30AM}

    15.2 ft. - Survey Abandoned - DOWNLEG UPSTREAM SIPHON(12:30AM}

Observations (15)

DistanceCodeObservation
10.8SMWSOIL VISIBLE 2 VOIDS
0MWM
15.2MSADOWNLEG UPSTREAM SIPHON(12:30AM}
10.8MGPSIDE SUPPORTS INSIDE VOID AT 12:00
14.8SMWSOIL VISIBLE 2 VOIDS
10.8MGPLOOKING UP THROUGH VOID TO METAL PLATES
2SAMSEVERE AGG
0AMH11:40AM
10.8SMWSOIL VISIBLE SECOND VOID AT 12:00
0MWL
0.6SRCLONG CIRCUM REWBAR CORRODED & MISSING
14.8SAMSEVERE AGG
10.8SMWSOIL VISIBLE VOID TO SURFACE
14.8SMW2 VOIDS AT 12:00
14.8SRCLONG CIRCUM REBAR CORRODED & MISSING

Properties (7)

additional_info
DOWNLEG UPSTREAM SIPHON
custom_field_three
SOIL VISIBLE VOIDS
custom_field_two
1
customer
LACSD
datetime
2021-01-03T23:27:47-08:00
documentation
MARTIN,RUVALCABA
is_lateral_inspection
false