Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2020, 07:38 PM
  • H 1236_H 1235_12172020_120540.mp4

Date
12/17/2020
W/O
859970
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01181
PipeID
P17161
Time
11:38 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8080
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
COVINA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
24
Purpose
Routine Assessment
Project
WO_859970_TV22032_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 1236
Downstream MH
H 1235
Dir. of Survey
Downstream
Length Surveyed
363.8 ft.
Total Length
363.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole H 1236 to H 1235
MH: H 1236MH: H 1235downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12362 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT START82.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"193.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"361.3 ft. MGO - General Observation - MAG COATING END361.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish363.8 ft. AMH - Downstream Manhole, Survey Ends - H 1235

Observations (10)

DistanceCodeObservation
82.9TB
361.9DAGS
2DAGS
361.3MGOMAG COATING END
193.2TBA
0MWM
363.8AMHH 1235
0MWL
2MGOMAG COAT START
0AMHH 1236

Properties (6)

custom_field_three
GREASE
custom_field_two
3
customer
1
datetime
2020-12-17T11:38:51-08:00
documentation
PRO PIPE
is_lateral_inspection
false