Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2020, 11:04 AM
  • H 1231_H 0586_12092020_031138.mp4

Date
12/09/2020
W/O
859970
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01181
PipeID
P17158
Time
3:04 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8238
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_859970_TV22032_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1231
Downstream MH
H 0586
Dir. of Survey
Downstream
Length Surveyed
184.1 ft.
Total Length
184.1 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
72
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
72
Pipe schematic from manhole H 1231 to H 0586
MH: H 1231MH: H 0586downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12310 ft. MWM - Water Mark, 35 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT17.7 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"64.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"72.4 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"167 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"181.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish184.1 ft. AMH - Downstream Manhole, Survey Ends - H 0586

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.1 ft. - General Observation - MAG COAT

Observations (11)

DistanceCodeObservation
0MWL
2.1SSS
0AMHH 1231
17.7TFC
2.1MGOMAG COAT
181.4SSS
184.1AMHH 0586
167TF
0MWM
64.6TFC
72.4TFC

Properties (6)

custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2020-12-09T03:04:16-08:00
documentation
PRO PIPE
is_lateral_inspection
false