Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2020, 09:33 AM
  • H 1277_H 1276_12072020_014407.mp4

Date
12/07/2020
W/O
859970
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01181
PipeID
P17202
Time
1:33 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8236
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
VINCENT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_859970_TV22032_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 1277
Downstream MH
H 1276
Dir. of Survey
Downstream
Length Surveyed
184.6 ft.
Total Length
184.6 ft.
Structural Index
3
Structural Quick
3F2F
Structural Rating
180
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
180
Pipe schematic from manhole H 1277 to H 1276
MH: H 1277MH: H 1276downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 12770 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK3.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"46.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"161.2 ft. MGO - General Observation - MAG COAT175.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"182.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish182.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish184.6 ft. AMH - Downstream Manhole, Survey Ends - H 1276184.6 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    12.6 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • General Observation - MAG COAT

    161.2 ft. - General Observation - MAG COAT

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"

    175.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"

Observations (14)

DistanceCodeObservation
182.3SSS
184.6AMHH 1276
0MWL
46.6TF
12.6TBA
3.1SAP
184.6MGOCONNECTION AT MH, 3 O'CLOCK
0MWM
182.3SAP
3.1SSS
161.2MGOMAG COAT
175.1TB
0AMHH 1277
0MGOCONNECTION AT MH, 9 O'CLOCK

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-12-07T01:33:56-08:00
documentation
PRO PIPE
is_lateral_inspection
false