Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2020, 05:33 AM
  • H 1267_H 1266_12072020_215850.mp4

Date
12/07/2020
W/O
859970
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01181
PipeID
P17192
Time
9:33 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8237
Sewer Name
H JOINT OUTFALL H - UNIT 8K
City
VINCENT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_859970_TV22032_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1267
Downstream MH
H 1266
Dir. of Survey
Downstream
Length Surveyed
356 ft.
Total Length
356 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
350
O&M Index
4
O&M Quick
4H00
O&M Rating
188
Overall Index
3
Overall Quick
Overall Rating
538
Pipe schematic from manhole H 1267 to H 1266
MH: H 1267MH: H 1266downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 12670 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"21.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"43 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"46.4 ft. LR - Alignment Right, 25 %, Start73.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"104.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"111.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"158.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"181.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"205.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 8"229.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"275.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"275.8 ft. LR - Alignment Right, 25 %, Finish283.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"307.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"314.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"332.6 ft. LL - Alignment Left, 35 %353 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK356 ft. AMH - Downstream Manhole, Survey Ends - H 1266

Observation photos (4)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 25 %, Start

    46.4 ft. - Alignment Right, 25 %, Start

  • Alignment Left, 35 %

    332.6 ft. - Alignment Left, 35 %

Observations (27)

DistanceCodeObservation
205.7TFA
353SSS
2.1SAP
356MGOCONNECTION AT MH, 3 O'CLOCK
283.5TF
158.5TF
104.3TF
73.5TF
181.8TF
229.1TF
314.7TF
46.4LR
21.1TF
332.6LL
2MGOMAG COAT
0AMHH 1267
0MWL
13.2TF
275.8TFA
307.7TF
275.8LR
356AMHH 1266
2SSS
43TF
111.6TF
0MWM
353SAP

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2020-12-07T21:33:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false