Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 24, 2020, 06:23 AM
  • C 0568_C 0567_12232020_223701.mp4

Date
12/23/2020
W/O
860133
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00362
PipeID
P04752
Time
10:23 PM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8089
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_860133_TV03084_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
18 in.
Upstream MH
C 0568
Downstream MH
C 0567
Dir. of Survey
Downstream
Length Surveyed
324.6 ft.
Total Length
324.6 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
227
Pipe schematic from manhole C 0568 to C 0567
MH: C 0568MH: C 0567downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 05680 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start85.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Start128.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: NO, Finish136.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start162.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish226.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start320.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish324.6 ft. AMH - Downstream Manhole, Survey Ends - C 0567

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    136.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    226.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0AMHC 0568
320.4DAGS
324.6AMHC 0567
85.9FL
136.2FL
320.4FL
0MWM
0MWL
2DAGS
162.6FL
128.6FL
226.2FL

Properties (7)

additional_info
630098122320201
custom_field_three
LONGITUDINAL FRACTURE
custom_field_two
3
customer
1
datetime
2020-12-23T22:23:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false