Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 24, 2020, 10:53 AM
  • C 0559_C 0558_12242020_030453.mp4

Date
12/24/2020
W/O
860133
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00362
PipeID
P04743
Time
2:53 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8089
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_860133_TV03084_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
C 0559
Downstream MH
C 0558
Dir. of Survey
Downstream
Length Surveyed
397.7 ft.
Total Length
397.7 ft.
Structural Index
2
Structural Quick
2E00
Structural Rating
56
O&M Index
2
O&M Quick
412O
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
216
Pipe schematic from manhole C 0559 to C 0558
MH: C 0559MH: C 0558downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05590 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start156.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start296.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish393.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish397.7 ft. AMH - Downstream Manhole, Survey Ends - C 0558

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    156.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
296.6CL
393.2DAGS
0MWL
0AMHC 0559
156.1CL
397.7AMHC 0558
0MWM
2DAGS

Properties (7)

additional_info
630098122320201
custom_field_three
LONGITUDINAL FRACTURE
custom_field_two
3
customer
1
datetime
2020-12-24T02:53:27-08:00
documentation
PRO PIPE
is_lateral_inspection
false