Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2020, 05:13 AM
  • 02 0111_02 0110_12142020_213132.mp4

Date
12/14/2020
W/O
860132
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00237
PipeID
P02278
Time
9:13 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8280
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_860132_TV02350_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
24 in.
Upstream MH
02 0111
Downstream MH
02 0110
Dir. of Survey
Downstream
Length Surveyed
313 ft.
Total Length
313 ft.
Structural Index
3
Structural Quick
433K
Structural Rating
198
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
202
Pipe schematic from manhole 02 0111 to 02 0110
MH: 02 0111MH: 02 0110downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01110 ft. MWM - Water Mark, 10 %of cross sectional area4.4 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES8.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start54.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"77 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: NO78 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - missed connection unknown if active or capped83.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.6 ft. H - Hole, at 10 o'clock, within 8 inches of joint: NO127.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"154.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.7 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES204.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"301.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS311 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish311 ft. MGO - General Observation - COCKROACHES IN MANHOLE313 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK313 ft. AMH - Downstream Manhole, Survey Ends - 02 0110

Observation photos (8)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    4.4 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: NO

    77 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: NO

  • Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - missed connection unknown if active or capped

    78 ft. - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - missed connection unknown if active or capped

  • Hole, at 10 o'clock, within 8 inches of joint: NO

    127.6 ft. - Hole, at 10 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    203.7 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    311 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (27)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
311CM
127.6H
228.9TFA
313MGOCONNECTION AT MH 9 O'CLOCK
0MWL
8.2CM
0AMH02 0111
252.2TF
175.2TF
154.3TF
78TFBmissed connection unknown if active or capped
104.1TF
54.2TFA
311DSZ
281.4TFC
4.4FM
203.7FM
0MWM
313AMH02 0110
127.7TF
83.8TFA
204.9TF
311MGOCOCKROACHES IN MANHOLE
77FM
231.7TF
301.7DSZDEBRIS

Properties (7)

additional_info
630069121420201
custom_field_three
MULTIPLE CRACKS/FRACTURES
custom_field_two
1
customer
1
datetime
2020-12-14T21:13:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false