Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2020, 10:13 AM
  • 04 0119_04 0118_12142020_022823.mp4

Date
12/14/2020
W/O
860498
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00411
PipeID
P11855
Time
2:13 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
12/14/20
Pre-Cleaning
No Pre-Cleaning
Media Label
K8279
Sewer Name
04 LA BREA AVENUE TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
02
Purpose
Routine Assessment
Project
WO_860498_TV04006_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
04 0119
Downstream MH
04 0118
Dir. of Survey
Downstream
Length Surveyed
324 ft.
Total Length
324 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
128
Pipe schematic from manhole 04 0119 to 04 0118
MH: 04 0119MH: 04 0118downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04 01190 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. MLC - Lining Change, Other (enter details in Field 39) - PE LINER10.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"14 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"26 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"58.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"69 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"104 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"295 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"308.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish324 ft. MGO - General Observation - COCKROACHES IN MANHOLE324 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK324 ft. AMH - Downstream Manhole, Survey Ends - 04 0118

Observation photos (2)

  • Lining Change, Other (enter details in Field 39) - PE LINER

    2 ft. - Lining Change, Other (enter details in Field 39) - PE LINER

  • General Observation - COCKROACHES IN MANHOLE

    324 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
0AMH04 0119
119.6TFA
295TFA
324MGOCOCKROACHES IN MANHOLE
321.9DAGS
0MWM
220.2TF
324MGOCONNECTION AT MH 9 O'CLOCK
154.7TFA
324AMH04 0118
10.4TFA
240.9TF
104TF
0MWL
69TFA
2DAGS
58.7TFA
26TFA
2MLCPE LINER
14TFA
206.2TFA
308.3TF

Properties (8)

additional_info
630069121420001
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-12-14T02:13:11-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PE_LINER