Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 14, 2020, 11:35 AM
  • 04 0117_04 0116_12142020_034931.mp4

Date
12/14/2020
W/O
860498
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00411
PipeID
P11853
Time
3:35 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8279
Sewer Name
04 LA BREA AVENUE TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
02
Purpose
Routine Assessment
Project
WO_860498_TV04006_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
04 0117
Downstream MH
04 0116
Dir. of Survey
Downstream
Length Surveyed
289.1 ft.
Total Length
289.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 04 0117 to 04 0116
MH: 04 0117MH: 04 0116downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04 01172 ft. MLC - Lining Change, Other (enter details in Field 39) - PE LINER2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start5.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"258 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"265.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish289.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE289.1 ft. AMH - Downstream Manhole, Survey Ends - 04 0116

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    289.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
2MLCPE LINER
2DAGS
46.5TF
289.1MGOCOCKROACHES IN MANHOLE
5.9TF
207.2TFA
287.4DAGS
265.3TBA
289.1AMH04 0116
0MWM
0MWL
158.2TFA
155.9TFA
107.6TFA
258TFA
0AMH04 0117
54.6TF
95.7TF

Properties (8)

additional_info
630069121420001
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-12-14T03:35:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false
lining
PE_LINER