Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2020, 08:59 AM
  • 02 1362_02 1361_12162020_011153.mp4

Date
12/16/2020
W/O
860134
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00277
PipeID
P03885
Time
12:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8287
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
11A
Purpose
Routine Assessment
Project
RFIR_WO_860134_TV02342_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
02 1361
Downstream MH
02 1362
Dir. of Survey
Upstream
Length Surveyed
271.4 ft.
Total Length
271.4 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
3
Overall Quick
Overall Rating
262
Pipe schematic from manhole 02 1361 to 02 1362
MH: 02 1361MH: 02 1362upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 13622.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish6.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"47.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"111.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"135.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"189.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"231 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"264.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start268 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"269.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start271.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE271.4 ft. MWM - Water Mark, 35 %of cross sectional area271.4 ft. MWL - Water Level, 25 %of cross sectional area271.4 ft. AMH - Downstream Manhole, Survey Begins - 02 1361

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    269.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
82.1TFA
269.1CM
3.4TFA
265.2TFA
223.6TFA
0MGOCOCKROACHES IN MANHOLE
0MWM
40.4TFA
159.5TFA
269.1MGOCOCKROACHES IN MANHOLE
0MWL
2DAGS
0AMH02 1361
136.3TFA
7.2CM
271.4AMH02 1362
269.1DAGS

Properties (7)

additional_info
630069121520204
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-16T00:59:56-08:00
documentation
PRO PIPE
is_lateral_inspection
false