Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 17, 2020, 05:54 AM
  • 18 0669_18 0668_12162020_221225.mp4

Date
12/16/2020
W/O
860087
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00696
PipeID
P14518
Time
9:54 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8288
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_860087_TV18081_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
349.5 ft.
Total Length
349.5 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
185
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
323
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06692 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23 ft. CS - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES42.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"49.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start96.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"211.4 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE CHIP IN PIPE299.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"347.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish347.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0668

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    23 ft. - Crack Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    49.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE CHIP IN PIPE

    211.4 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES - POSSIBLE CHIP IN PIPE

Observations (17)

DistanceCodeObservation
0MWL
49.7CM
23CS
0MWM
305.1TFC
2DAGS
202.8TFC
211.4HPOSSIBLE CHIP IN PIPE
349.5AMH18 0668
96.1TFA
347.2DAGS
0AMH18 0669
197.6TFC
42.6TBA
101.3TFA
347.2CM
299.6TFC

Properties (7)

additional_info
630069121620201
custom_field_three
MULTIPLE CRACKS/HOLE
custom_field_two
2
customer
1
datetime
2020-12-16T21:54:45-08:00
documentation
PRO PIPE
is_lateral_inspection
false