- Date
- 12/16/2020
- W/O
- 860137
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z01184
- PipeID
- P25882
- Time
- 12:12 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8249
- Sewer Name
- H JOINT OUTFALL H - UNIT 8L RELIEF
- City
- AZUSA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 12
- Purpose
- Routine Assessment
- Project
- WO_860137_TV22099_NOV2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- H 1339
- Downstream MH
- H 1338
- Dir. of Survey
- Downstream
- Length Surveyed
- 217.3 ft.
- Total Length
- 217.3 ft.
- Structural Index
- 2
- Structural Quick
- 312B
- Structural Rating
- 37
- O&M Index
- 2
- O&M Quick
- 2G00
- O&M Rating
- 82
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 119
Pipe schematic from manhole H 1339 to H 1338 Observation photos (4)

10.7 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

17.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

18.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

21.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start