Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2020, 09:45 AM
  • 01 0527A_01 0527A1_12152020_015350.mp4

Date
12/15/2020
W/O
860479
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P26773
Time
1:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8282
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_860479_TV01017_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 0527A
Downstream MH
01 0527A1
Dir. of Survey
Downstream
Length Surveyed
213.8 ft.
Total Length
213.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0527A to 01 0527A1
MH: 01 0527AMH: 01 0527A1downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0527A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start85.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"186.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"212.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish213.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0527A1213.8 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK

Observation photos (2)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWM
213.8AMH01 0527A1
85.9TFC
87.9TFC
0MGOCOCKROACHES IN MANHOLE
148.1TFC
212.1DAGS
2DAGS
145.1TFC
0MWL
0AMH01 0527A
0MGOCONNECTION AT MH 9 O'CLOCK
186.4TFC
213.8MGOCONNECTION AT MH 12 O'CLOCK

Properties (7)

additional_info
630069121420203
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2020-12-15T01:45:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false