Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 15, 2020, 09:22 AM
  • 01 0529_01 0528_12152020_013028.mp4

Date
12/15/2020
W/O
860479
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01016
Time
1:22 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8282
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_860479_TV01017_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0529
Downstream MH
01 0528
Dir. of Survey
Downstream
Length Surveyed
134.4 ft.
Total Length
134.4 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
2
O&M Quick
412D
O&M Rating
56
Overall Index
3
Overall Quick
Overall Rating
134
Pipe schematic from manhole 01 0529 to 01 0528
MH: 01 0529MH: 01 0528downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05290 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"33.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish132.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish134.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE134.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0528

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    134.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
108.8TFC
33.7TFC
132.7CM
110.6TFC
0MWL
134.4MGOCOCKROACHES IN MANHOLE
134.4AMH01 0528
0AMH01 0529
132.7DAGS
2DAGS
14.1TFC
60.2TFC
0MWM
2CM

Properties (7)

additional_info
630069121420203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2020-12-15T01:22:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false