Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2020, 12:14 PM
  • 01 0523_01 0522_12072020_042709.mp4

Date
12/07/2020
W/O
860479
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00206
PipeID
P01008
Time
4:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8267
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_860479_TV01017_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0522
Downstream MH
01 0523
Dir. of Survey
Upstream
Length Surveyed
251.9 ft.
Total Length
251.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3A2G
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
112
Pipe schematic from manhole 01 0522 to 01 0523
MH: 01 0522MH: 01 0523upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 01 05230 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK1.9 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - UNKNOWN1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish7.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"10 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start100.9 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS101.9 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish105 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.5 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start153.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 03 o'clock, , within 8 inches of joint: YES, Finish156.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"222 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"249.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start251.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0522251.9 ft. MWM - Water Mark, 40 %of cross sectional area251.9 ft. MWL - Water Level, 20 %of cross sectional area251.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK251.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 20 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES, Start

    98.4 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    251.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (28)

DistanceCodeObservation
251.9MGOCOCKROACHES IN MANHOLE
251.9AMH01 0523
0AMH01 0522
150DAGS
0MWM
141.1TFC
0MWL
26TFC
98.4DAGS
191.4TFC
244.6TFC
95.6TFC
151DAGS
98.4DAGS
28.6TBA
29.9TFC
250DSZUNKNOWN
197.6TFC
251.9MGOCONNECTION AT MH 3 O'CLOCK
151DSZDEBRIS
241.9TFC
146.9TFC
91TF
250DAGS
0MGOCONNECTION AT MH 9 O'CLOCK
4.6TFC
0MGOCOCKROACHES IN MANHOLE
2DAGS

Properties (7)

additional_info
630069120720003
custom_field_three
GREASE
custom_field_two
4
customer
1
datetime
2020-12-07T04:14:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false