Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 11, 2020, 10:06 AM
  • 01 0779_G 0154_12112020_023333.mp4

Date
12/11/2020
W/O
860088
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00892
PipeID
P01478
Time
2:06 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8278
Sewer Name
01 BULLIS ROAD TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_860088_TV01203_NOV2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
48 in.
Upstream MH
01 0779
Downstream MH
G 0154
Dir. of Survey
Downstream
Length Surveyed
188.5 ft.
Total Length
188.9 ft.
Structural Index
4
Structural Quick
5C42
Structural Rating
152
O&M Index
2
O&M Quick
2F00
O&M Rating
74
Overall Index
3
Overall Quick
Overall Rating
226
Pipe schematic from manhole 01 0779 to G 0154
MH: 01 0779MH: G 0154downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 07790 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start18.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"20.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - POSSIBLE HOLE IN TAP "BEFORE CAP"23.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"66.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. FH3 - Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES, Start75.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish99 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"151.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"163.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start163.5 ft. FH3 - Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish167.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish179.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start188.5 ft. AOC - Drop Connection, Survey Ends - G 0154188.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish188.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish188.5 ft. TFA - Tap Factory Made Active, at 06 o'clock, -, within 8 inches of joint: YES, 12" - DROP CONNECTION

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    75.8 ft. - Fracture Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    163.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    179.5 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Drop Connection, Survey Ends - G 0154

    188.5 ft. - Drop Connection, Survey Ends - G 0154

Observations (26)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
163.5FL
20.2TFCPOSSIBLE HOLE IN TAP "BEFORE CAP"
120.5TFC
75.8FH3
18.4TFC
147.4TFC
188.5AOCG 0154
99TF
0MWL
23.1TBA
68.5TFC
2FL
75.8FL
167.8TFC
188.5DAGS
0AMH01 0779
179.5FL
66.3TFC
188.5FM
0MWM
188.5TFADROP CONNECTION
179.5FM
151.7TBA
163.5FH3
2DAGS

Properties (7)

additional_info
630069121020204
custom_field_three
HINGE FRACTURES/MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2020-12-11T02:06:03-08:00
documentation
PRO PIPE
is_lateral_inspection
false