- Date
- 12/21/2020
- W/O
- 0859964
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00432
- PipeID
- P05586
- Time
- 2:18 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1677
- Sewer Name
- 05 DISTRICT #5 MAIN RELIEF TRUNK
- City
- HAWTHORNE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 13
- Purpose
- Routine Assessment
- Project
- 20201221MDM_DISTRICT_5_MAIN_RELIEF_TRUNK
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 30 in.
- Upstream MH
- 05 2071
- Downstream MH
- 05 0369
- Dir. of Survey
- Downstream
- Length Surveyed
- 305.7 ft.
- Total Length
- 305.7 ft.
- Structural Index
- 2
- Structural Quick
- 2300
- Structural Rating
- 6
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole 05 2071 to 05 0369 Observation photos (5)

0 ft. - Water Mark, 80 %of cross sectional area

2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - General Observation - MAG COAT 99%

94.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

294.5 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE