Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2020, 02:02 PM
  • 22 0098_22 0097_12082020_220700.mp4

Date
12/08/2020
W/O
860500
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00805
PipeID
P16339
Time
6:02 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8073
Sewer Name
22 DISTRICT #22 MAIN TRUNK
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
WO_860500_TV22092_NOV2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
22 0098
Downstream MH
22 0097
Dir. of Survey
Downstream
Length Surveyed
254.6 ft.
Total Length
254.6 ft.
Structural Index
2
Structural Quick
2I00
Structural Rating
100
O&M Index
2
O&M Quick
412I
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
204
Pipe schematic from manhole 22 0098 to 22 0097
MH: 22 0098MH: 22 0097downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 00980 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - MAG COAT START2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT SPALLING THROUGHOUT52.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"69.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"108.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"125.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"189.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"249.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish250 ft. MGO - General Observation - MAG COAT END251 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish254.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0097254.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK254.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observations (20)

DistanceCodeObservation
52.3TFC
164.3TFC
2MGOMAG COAT START
254.6AMH22 0097
116.9TF
254.6MGOCONNECTION AT MH 3 O'CLOCK
125.1TFC
0MGOCONNECTION AT MH 3 O'CLOCK
0AMH22 0098
108.9TFA
250MGOMAG COAT END
254.6MGOCONNECTION AT MH 9 O'CLOCK
3SSSSLIGHT SPALLING THROUGHOUT
69.9TFC
251SSS
0MWM
0MWL
249.9DAGS
2DAGS
189.9TFC

Properties (7)

additional_info
630075120820201
custom_field_three
GRAESE
custom_field_two
3
customer
1
datetime
2020-12-08T06:02:26-08:00
documentation
PRO PIPE
is_lateral_inspection
false