Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2020, 07:58 AM
  • H 1283_22 0872_12042020_001133.mp4

Date
12/03/2020
W/O
855105
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00803
PipeID
P17240
Time
11:58 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8231
Sewer Name
DALTON TRUNK, SECTION 3
City
AZUSA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_854956_TV22105_OCT2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
H 1283
Downstream MH
22 0872
Dir. of Survey
Downstream
Length Surveyed
282.1 ft.
Total Length
282.1 ft.
Structural Index
3
Structural Quick
5J3J
Structural Rating
560
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
560
Pipe schematic from manhole H 1283 to 22 0872
MH: H 1283MH: 22 0872downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - H 12830 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 12 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2 ft. MGO - General Observation - 80% MAG COAT2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"53.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"92.3 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"154.9 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES211.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"234.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"278.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish282.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0872282.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE

Observation photos (4)

  • General Observation - 80% MAG COAT

    2 ft. - General Observation - 80% MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

    154.9 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
2MGO80% MAG COAT
154.9SRV
2SRV
282.1AMH22 0872
282.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
53.7TFC
234.9TFC
0MWL
0MGOROACHES @ MH
53.9TFC
280SRV
211.8TFC
2SSS
92.3TFC
278.8SSS
0AMHH 1283
0MWM
0MGOCONN @ MH 12 O'CLOCK/ACTIVE
278.8SAP
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SAP
0MGOCONN @ MH 9 O'CLOCK/ACTIVE

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
1
datetime
2020-12-03T23:58:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false